Fire detection quantity estimate
Get a budget-level quantity for a fire alarm system before the designer has drawn it. The fire code and fire authority decide the final design.
Result
Detectors
75
25 per floor, 50 m² each in practice
Manual call points
6
2 per floor, at the exits
Sounders / strobes
12
Fire zones
3
About one per 1,500 m² per floor
Panel loops
1
112 addressable devices incl. 20% spare
- Check:Placement, zones, sounder levels and call-point spacing are set by the fire code and the fire authority for your building. This is a first count for budgeting, not a design.
Method
How the numbers are worked out
Detectors
Floor area per floor divided by a practical coverage per detector (50 m² smoke, 30 m² heat; the code's maximum spacing is wider, but rooms, corridors and beams cut it), plus an allowance for obstructions.
Call points, sounders, zones
Call points go at exits on each floor; sounders are about one per 250 m² per floor, at least two; zones are about one per 1,500 m² on a floor.
Panel loops
Addressable loops commonly carry up to about 125 devices with spare capacity.
Assumptions and limits
- This is a quantity for a budget, not a detector layout. Rooms, risers, plant spaces and voids each need their own treatment.
- Sounder levels, call-point travel distances and detection type are fixed by the National Building Code and the local fire authority for the occupancy.
- Fire systems should be designed, commissioned and approved by qualified people.