Planning tool

Fire detection quantity estimate

Get a budget-level quantity for a fire alarm system before the designer has drawn it. The fire code and fire authority decide the final design.

Building
m²
m
Detection
%
%

Result

Detectors

75

25 per floor, 50 m² each in practice

Manual call points

6

2 per floor, at the exits

Sounders / strobes

12

Fire zones

3

About one per 1,500 m² per floor

Panel loops

1

112 addressable devices incl. 20% spare

  • Check:Placement, zones, sounder levels and call-point spacing are set by the fire code and the fire authority for your building. This is a first count for budgeting, not a design.

Method

How the numbers are worked out

Detectors

Floor area per floor divided by a practical coverage per detector (50 m² smoke, 30 m² heat; the code's maximum spacing is wider, but rooms, corridors and beams cut it), plus an allowance for obstructions.

Call points, sounders, zones

Call points go at exits on each floor; sounders are about one per 250 m² per floor, at least two; zones are about one per 1,500 m² on a floor.

Panel loops

Addressable loops commonly carry up to about 125 devices with spare capacity.

Assumptions and limits

  • This is a quantity for a budget, not a detector layout. Rooms, risers, plant spaces and voids each need their own treatment.
  • Sounder levels, call-point travel distances and detection type are fixed by the National Building Code and the local fire authority for the occupancy.
  • Fire systems should be designed, commissioned and approved by qualified people.

Related

Nothing you type here leaves your device unless you choose to send it to us. These are planning estimates; a survey or the equipment data sheet confirms the final figures.

Want an engineer to check it?

Send us what you worked out and we will come back with a design based on the real site.