Planning tool
Generator (DG set) sizing
Turn a connected load into a standard generator rating, with margin for growth and for heat and altitude.
Result
Generator size
125kVA
Needs 114 kVA
Output at 0.8 pf
100kW
Running load
90kVA
72 kW at 0.8 power factor
Load on the set
72%
Fuel use (diesel)
19.4L/h
About 0.27 litre per kWh
- Check:Large motors (lifts, pumps, air conditioners) and UPS inputs can draw a lot as they start. Give the supplier your largest starting loads; the set may need to be bigger.
Method
How the numbers are worked out
From kW to kVA
The generator is rated in kVA. The running load in kW divided by its power factor gives kVA; growth, safety margin and derating are then added.
Standard ratings
The result is rounded up to the next common DG set rating.
Assumptions and limits
- Motor starting (lifts, pumps, compressors) can need more than the running figure. Give the supplier your largest motors and how they start.
- Fuel use of 0.27 L per kWh is a rule of thumb for diesel at good load.
- Rules on noise, emissions and fuel storage vary by location.
Related
Nothing you type here leaves your device unless you choose to send it to us. These are planning estimates; a survey or the equipment data sheet confirms the final figures.