Generator (DG set) sizing

Turn a connected load into a standard generator rating, with margin for growth and for heat and altitude.

Load
kW

The load that must run during a power cut, including the UPS input.

%
Set
%
%

Engines lose power in heat and thin air; ask the supplier for the figure.

Result

Generator size

125kVA

Needs 114 kVA

Output at 0.8 pf

100kW

Running load

90kVA

72 kW at 0.8 power factor

Load on the set

72%

Fuel use (diesel)

19.4L/h

About 0.27 litre per kWh

  • Check:Large motors (lifts, pumps, air conditioners) and UPS inputs can draw a lot as they start. Give the supplier your largest starting loads; the set may need to be bigger.

Method

How the numbers are worked out

From kW to kVA

The generator is rated in kVA. The running load in kW divided by its power factor gives kVA; growth, safety margin and derating are then added.

Standard ratings

The result is rounded up to the next common DG set rating.

Assumptions and limits

  • Motor starting (lifts, pumps, compressors) can need more than the running figure. Give the supplier your largest motors and how they start.
  • Fuel use of 0.27 L per kWh is a rule of thumb for diesel at good load.
  • Rules on noise, emissions and fuel storage vary by location.

Related

Nothing you type here leaves your device unless you choose to send it to us. These are planning estimates; a survey or the equipment data sheet confirms the final figures.